An air-conditioning system operates at a total pressure of 95kPa and consists of a heating section and a humidifier that supplies wet steam (saturated water vapor) at 100°C. Air enters the heating section at 10°C and 70% relative humidity at a rate of 35 m^3/min, and it leaves the humidifying section at 20°C and 60 percent relative humidity. Determine:

(a) the temperature and relative humidity of air when it leaves the heating section.

(b) the rate of heat transfer in the heating section.

(c) the rate at which water is added to the air in the humidifying section.

+3
Answers (1)
  1. 14 January, 04:45
    0
    The temperature and relative humidity when it leaves the heating section = T2 = 19° C and ∅2 = 38%

    Heat transfer to the air in the heating section = Qin = 420 KJ/min

    Amount of water added = 0.15 KG/min

    Explanation:

    The Property of air can be calculated at different states from the psychometric chart.

    At T1 = 10° C and ∅ = 70%

    h1 = 87 KJ/KG of dry air

    w1 = 0.0053 kg of moist air / kg of dry air

    v1 = 0.81 m^3/kg

    AT T3 = 20° C, 3 ∅ = 60%

    h3 = 98 KJ/KG of dry air

    w3 = 0.0087 kg of moist air / kg of dry air

    The moisture in the heating system remains the same when flowing through the heating section hence, (w1 = w2)

    The mass flow rate of dry air,

    m1 = V'1/V1 = 35/0.81

    m1 = 43.21 kg/min

    By balancing the energy in heating section we get:

    mwhw + ma2h2 = mah3

    (w3 - w2) hw + h2 = h3

    h2 = h3 - (w3 - w2) hw @ 100 C

    Hence, hw = hg @ 100 C and w2 = w1

    h2 = h3 - (w3 - w2) hg @ 100 C

    h2 = 98 - (0.0087 - 0.0053) * 2676

    h2 = 33.2 KJ/KG

    The exit temperature and humidity will be,

    T2 = 19.5° C and 2 ∅ = 37.8%

    (b) Calculating the transfer of heat in the heating section

    Qin = ma (h2 - h1) = 43.21 (33.2 - 23.5)

    Qin = 420 KJ/min

    (c) Rate at which water is added to the air in the humidifying section,

    mw = ma (w3 - w2) = (43.2) (0.0087 - 0.0053)

    mw = 0.15 KG/min
Know the Answer?
Not Sure About the Answer?
Find an answer to your question 👍 “An air-conditioning system operates at a total pressure of 95kPa and consists of a heating section and a humidifier that supplies wet steam ...” in 📗 Engineering if the answers seem to be not correct or there’s no answer. Try a smart search to find answers to similar questions.
Search for Other Answers