Ask Question
27 December, 14:31

Several 4-conductor cables are installed in a ladder cable tray without a cover and without exceeding the cable tray fill limit. Each 4-conductor cable comprises four 1/0 AWG THHN copper conductors, each of which is considered current-carrying. What is the allowable ampacity of each 1/0 AWG THHN copper conductor?

+3
Answers (1)
  1. 27 December, 14:45
    0
    Answer: The allowable ampacity is 136 amperes

    Explanation:According to the National Electrical Code the ampacity for insulated conductors of type 1/0 AWG THHN is 170 amperes (from tables) for cables no exceeding 3

    But we are presented with 4 cables in a tray,

    Going by the National Electrical Code where conductors exceeds 3, the allowable ampacity shall be reduced to 80% the of the ampacity gotten from table.

    Hence the allowable ampacity for 4 copper cables of type 1/0 AWG THHN is (80/100) * 170=136 Amperes
Know the Answer?
Not Sure About the Answer?
Find an answer to your question 👍 “Several 4-conductor cables are installed in a ladder cable tray without a cover and without exceeding the cable tray fill limit. Each ...” in 📗 Physics if the answers seem to be not correct or there’s no answer. Try a smart search to find answers to similar questions.