Problem 3.

A 1.8 m wide by 1.0 m tall by 0.65m deep home freezer is insulated with 5.0cm thick Styrofoam insulation. At what rate must the compressor remove heat from the freezer to keep the inside at (-20°C) in a room where the air temperature is 25°C.

+2
Answers (1)
  1. 5 March, 13:48
    0
    143.352 watt.

    Explanation:

    So, in the question above we are given the following parameters or data or information that is going to assist us in answering the question above efficiently. The parameters are:

    "A 1.8 m wide by 1.0 m tall by 0.65m deep home freezer is insulated with 5.0cm thick Styrofoam insulation"

    The inside temperature of the freezer = - 20°C.

    Thickness = 5.0cm = 5.0 * 10^-2 m.

    Step one: Calculate the surface area of the freezer. That can be done by using the formula below:

    Area = 2[ (Length * breadth) + (breadth * height) + (length * height) ].

    Area = 2[ (1.8 * 0.65) + (0.65 * 1.0) + (1.8 * 1.0) ].

    Area = 7.24 m^2.

    Step two: Calculate the rate of heat transfer by using the formula below;

    Rate of heat transfer = [ thermal conductivity * Area (T1 - T2) ] / thickness.

    Rate of heat transfer = 0.022 * 7.24 (25+20) / 5.0 * 10^-2 = 143.352 watt.
Know the Answer?
Not Sure About the Answer?
Find an answer to your question 👍 “Problem 3. A 1.8 m wide by 1.0 m tall by 0.65m deep home freezer is insulated with 5.0cm thick Styrofoam insulation. At what rate must the ...” in 📗 Physics if the answers seem to be not correct or there’s no answer. Try a smart search to find answers to similar questions.